Exciter Model: ESAC8B_GE

 

Model Equations and/or Block Diagrams

Parameters:

Tr Filter time constant, sec
Kpr Proportional gain, pu
Kir Integral gain, pu
Kdr Regulator derivative gain, pu
Tdr Regulator derivative washout time constant, sec
Vrmax Maximum exciter control signal, pu
Vrmin Minimum exciter control signal, pu
Ka Voltage regulator gain
Ta Voltage regulator time constant, sec
Te Exciter field time constant, sec
Vfemax Exciter field current limit parameter, pu
Vemin Minimimum exciter output voltage, pu
Ke Exciter field resistance constant, pu
Kc Rectifier loading factor proportional to commutating reactance
Kd Exciter internal reactance, pu
E1 Field voltage value, 1
SE1 Saturation factor at E1
E2 Field voltage value, 2
SE2 Saturation factor at E2
VTMult If non-zero, multiply Vrmax and Vrmin by terminal voltage
Spdmlt If not zero, multiply output (Efd) by generator speed